Presentation | Highly efficient, easy-to-deploy 120kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5×8 start-up service. See the battery runtime chart for details. |
---|---|
Lead time | Usually Ships within 2 Weeks |
Main Input Voltage | 400 V 3 phases |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V |
Rated power in W | 120 kW |
Rated power in VA | 120 kVA |
Battery type | External battery system Li-Ion (Lithium-Ion) VRLA |
Provided equipment | Cat 5 Ethernet cable EcoStruxure Ready (UPS) Dust filter Installation guide Integrated network management Power modules ship installed Start-up service |
Bypass voltage tolerance | +/- 10 % |
---|---|
Redundant | No |
Colour | White |
---|---|
Height | 148.5 cm |
Width | 52.1 cm |
Depth | 84.7 cm |
Net weight | 290 kg |
USB compatible | No |
Network frequency | 40…70 Hz |
---|---|
Input voltage limits | 340…460 V 400 V |
Maximum input current | 216 A |
Max short time withstand current | 65 kA |
Input harmonic distortion | Less than 3 % for full load |
Load power factor | From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load | 0.99 |
Maximum configurable power in W | 120 kW |
---|---|
Output frequency | 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
Crest factor | 2.5 |
Wave type | Sine wave |
Output voltage tolerance | +/-1% after 50ms |
Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
Bypass type | Built-in static bypass |
Maximum configurable power in VA | 120 kVA |
Standards | IEC 62040-1-1 IEC 62040-2 IEC 60721-4-2 level 2M2 OSHPD UL 1778 5th edition |
---|
Ambient air temperature for operation | 0…40 °C |
---|---|
Relative humidity | 0…95 % non-condensing |
Operating altitude | 0…3333 ft |
Ambient air temperature for storage | -24…55 °C |
Storage Relative Humidity | Non-condensing 10…80 % |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 65 dBA |
Heat dissipation | 12509 Btu/h |
IP degree of protection | IP21 |
Efficiency | View Efficiency Graph |
---|---|
Battery voltage | 480…576 V DC |
Discharge battery voltage | 384 V DC |
Max current discharge | 326 A |
Battery power in VAH | 0 VAh runtime |
Extended runtime | 0 |
Free slots | 1 |
---|---|
Control panel | Touch screen LCD user interface |
Alarm | Audible and visible alarms prioritized by severity |
Unit Type of Package 1 | Db |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 168 cm |
Package 1 Width | 99 cm |
Package 1 Length | 64 cm |
Package 1 Weight | 315 kg |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
---|
brands | Benicia Bed Foundry |
---|---|
color | Violet |