GVSUPS40KHINS

GVSUPS40KHINS

40kVA Online Double Conversion Galaxy UPS kVA = kW 3Ph input 3 Phase output

Documents

Enquire Now

Information

Description

Overview
Presentation Highly efficient, easy-to-deploy 40kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5×8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.
Lead time Usually Ships within 2 Weeks
Main
Main Input Voltage 400 V 3 phases
Other Input Voltage 380 V
415 V
Main Output Voltage 400 V 3 phases
Other Output Voltage 380 V
415 V
Rated power in W 40 kW
Rated power in VA 40 kVA
Output connector type Hard wire 5-wire (3P + N + E) 1
Battery type External battery system
Li-Ion (Lithium-Ion)
VRLA
Provided equipment Dust filter
Installation guide
Integrated network management
Power modules ship installed
Start-up service
Top and bottom cable entry
General
Bypass voltage tolerance +/- 10 %
Max bypass input current 64 A
Redundant No
Physical
Colour White
Height 148.5 cm
Width 52.1 cm
Depth 84.7 cm
Net weight 210 kg
USB compatible No
Input
Network frequency 40…70 Hz
Number of input connectors 1 hard wire 4-wire (3P + E)
1 hard wire 5-wire (3P + N + E)
Input voltage limits 340…460 V 400 V
Maximum input current 74 A
Max short time withstand current 65 kA
Input harmonic distortion Less than 3 % for full load
Load power factor From 0.7 leading to 0.7 lagging without any derating
Input Power Factor at Full Load 0.99
Output
Maximum configurable power in W 40 kW
Harmonic distortion Less than 3 %
Output frequency 50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
Crest factor 2.5
Wave type Sine wave
Output voltage tolerance +/-1% after 50ms
Output harmonic distortion < 1% linear load and < 3% non-linear load
Output overload operation 10 minutes at 125% and 60 seconds at 150%
Bypass type Built-in static bypass
Maximum configurable power in VA 40 kVA
Conformance
Product certifications FCC part 15 class A
UL 1778 5th edition
standards CSA C22.2 No 107.3
EN/IEC 62040-1
EN/IEC 62040-2
EN/IEC 62040-3
IEC 60721-4-2 level 2M2
Environmental
Ambient air temperature for operation 0…40 °C
Relative humidity 0…95 % non-condensing
Operating altitude 0…3281 ft
Ambient air temperature for storage -25…55 °C
Storage Relative Humidity 10…80 % Non-condensing
Storage altitude 0.00…15240.00 m
Acoustic level 65 dBA
Heat dissipation 3845.4 Btu/h
IP degree of protection IP21
Batteries & Runtime
Efficiency View Efficiency Graphaction_new_window
Battery voltage 384…576 V DC
Discharge battery voltage 307 V DC
Max current discharge 136 A
Battery power in VAH 0 VAh runtime
Extended runtime 0
Communications & Management
Free slots 1
Control panel Touch screen LCD user interface
Alarm Audible and visible alarms prioritized by severity
Packing Units
Unit Type of Package 1 Db
Number of Units in Package 1 1
Package 1 Height 168 cm
Package 1 Width 99 cm
Package 1 Length 64 cm
Package 1 Weight 235 kg
Contractual warranty
Warranty 1 year on-site repair or replace with factory authorized Start-Up